This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0650017 , Pineville Water Association #3
34 of the 73 analytes this system has been tested for have been detected at least once, across 182 samples on record.
The other 39 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 182 samples on record, detections range from October 27, 2003 to March 24, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 30 of 30 results | Jul 18, 2007 | Aug 2, 2023 |
| Lead 1030 | Inorganic Chemical | 19 of 30 results | Jul 18, 2007 | Aug 2, 2023 |
| Barium 1010 | Inorganic Chemical | 14 of 14 results | Oct 27, 2003 | Mar 24, 2025 |
| Fluoride 1025 | Inorganic Chemical | 14 of 15 results | Oct 27, 2003 | Mar 24, 2025 |
| Xylenes, Total 2955 | Organic Chemical | 12 of 61 results | Aug 18, 2009 | Aug 11, 2014 |
| Chromium 1020 | Inorganic Chemical | 10 of 14 results | Oct 27, 2003 | Mar 24, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 7 of 7 results | Aug 16, 2004 | Feb 24, 2025 |
| TTHM 2950 | Organic Chemical | 7 of 7 results | Aug 16, 2004 | Feb 24, 2025 |
| Nickel 1036 | Inorganic Chemical | 6 of 14 results | Mar 29, 2004 | May 10, 2017 |
| Gross Alpha Particle Activity 4109 | Radionuclide | 6 of 8 results | Jun 26, 2012 | Jan 15, 2013 |
| Ethylbenzene 2992 | Organic Chemical | 5 of 62 results | Aug 18, 2009 | Aug 9, 2010 |
| Dichloroacetic Acid 2451 | Organic Chemical | 4 of 4 results | Sep 12, 2007 | Aug 24, 2016 |
| Trichloroacetic Acid 2452 | Organic Chemical | 4 of 4 results | Sep 12, 2007 | Aug 24, 2016 |
| Chloroform 2941 | Organic Chemical | 4 of 4 results | Sep 12, 2007 | Aug 24, 2016 |
| Bromodichloromethane 2943 | Organic Chemical | 4 of 4 results | Sep 12, 2007 | Aug 24, 2016 |
| Dibromochloromethane 2944 | Organic Chemical | 4 of 4 results | Sep 12, 2007 | Aug 24, 2016 |
| Sulfate 1055 | Inorganic Chemical | 3 of 3 results | Oct 27, 2003 | May 27, 2010 |
| Styrene 2996 | Organic Chemical | 1 of 62 results | Aug 6, 2013 | Aug 6, 2013 |
| Calcium 1016 | Inorganic Chemical | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Chloride 1017 | Inorganic Chemical | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Manganese 1032 | Inorganic Chemical | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Potassium 1042 | Inorganic Chemical | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Sodium 1052 | Inorganic Chemical | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Residue, Total, Filterable 1057 | Water Quality | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Alkalinity, Caco3 Stability 1067 | Water Quality | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Carbon Dioxide 1901 | Water Quality | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Color 1905 | Water Quality | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Hardness, Total (As Caco3) 1915 | Water Quality | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Alkalinity, Total 1927 | Water Quality | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Iron, Field Result FEFD | Inorganic Chemical | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Calculated Sodium NACA | Water Quality | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| PH, Field Result PHFD | Water Quality | 1 of 1 result | May 27, 2010 | May 27, 2010 |
| Selenium 1045 | Inorganic Chemical | 1 of 14 results | Feb 8, 2010 | Feb 8, 2010 |
| Carbon Tetrachloride 2982 | Organic Chemical | 1 of 62 results | Dec 6, 2004 | Dec 6, 2004 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 11–20 of 182 samples, newest first — collected December 5, 2022 to October 30, 2023. The summary above covers all 182.
37 results from the 10 samples listed here: 15 detected, 22 not detected. Across the whole record it is 170 of 1,737. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
We withheld the location of 5 sampling points below. The location on record identifies a private home, and we do not publish those. That is our decision, not the agency’s. The sampling point, its type and every result taken there are published unchanged.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Oct 30, 2023 12:35, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Oct 30, 2023 12:35, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Oct 30, 2023 12:35, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
|
||
| 0.0844 mg/l , sample collected Aug 2, 2023 06:15, sampling point LC0001 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| 1.6 ug/l , sample collected Aug 2, 2023 06:15, sampling point LC0001 | Lead 1030 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
|
||
| 0.0569 mg/l , sample collected Aug 1, 2023 07:00, sampling point LC0003 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| 0.6 ug/l , sample collected Aug 1, 2023 07:00, sampling point LC0003 | Lead 1030 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
|
||
| 0.111 mg/l , sample collected Aug 1, 2023 10:30, sampling point LC0002 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Aug 1, 2023 10:30, sampling point LC0002 | Lead 1030 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
|
||
| 0.0549 mg/l , sample collected Aug 1, 2023 06:30, sampling point LC0004 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| 0.9 ug/l , sample collected Aug 1, 2023 06:30, sampling point LC0004 | Lead 1030 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
|
||
| 0.0737 mg/l , sample collected Aug 1, 2023 06:05, sampling point LC0009 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| 0.5 ug/l , sample collected Aug 1, 2023 06:05, sampling point LC0009 | Lead 1030 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Jul 11, 2023 13:30, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2021 – Dec 31, 2023 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 15, 2023 13:30, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| 0.0019 mg/l , sample collected May 15, 2023 13:30, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 15, 2023 13:30, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| 0.0008 mg/l , sample collected May 15, 2023 13:30, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| 0.151 mg/l , sample collected May 15, 2023 13:30, sampling point TF102 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2021 – Dec 31, 2023 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 15, 2023 13:30, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 15, 2023 13:30, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected May 15, 2023 13:30, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 15, 2023 13:30, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 15, 2023 13:30, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 15, 2023 13:30, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2021 – Dec 31, 2023 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0036 mg/l , sample collected Dec 5, 2022 12:30, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.171 mg/l , sample collected Dec 5, 2022 12:30, sampling point TF101 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 5, 2022 12:30, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| 9.58 ug/l , sample collected Dec 5, 2022 12:30, sampling point MRT000 | Total Haloacetic Acids (Haa5) 2456 EPA method 552.2 | Jan 1, 2020 – Dec 31, 2022 |
-
- Collected
- Oct 30, 2023 12:35
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- NI-231031-042
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2023 – Dec 31, 2023
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Aug 2, 2023 06:15
- Sampling point
- LC0001 Location withheld
- Sample type
- Routine
- Lab sample
- PB-230802-005
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0844 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 1.6 ug/l
-
- Collected
- Aug 1, 2023 07:00
- Sampling point
- LC0003 Location withheld
- Sample type
- Routine
- Lab sample
- PB-230802-002
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0569 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.6 ug/l
-
- Collected
- Aug 1, 2023 10:30
- Sampling point
- LC0002 Location withheld
- Sample type
- Routine
- Lab sample
- PB-230802-004
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.111 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Aug 1, 2023 06:30
- Sampling point
- LC0004 Location withheld
- Sample type
- Routine
- Lab sample
- PB-230802-001
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0549 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.9 ug/l
-
- Collected
- Aug 1, 2023 06:05
- Sampling point
- LC0009 Location withheld
- Sample type
- Routine
- Lab sample
- PB-230802-003
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0737 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.5 ug/l
-
- Collected
- Jul 11, 2023 13:30
- Sampling point
- TF102 Treatement Facility TF102
- Sample type
- Routine
- Lab sample
- CN-230712-014
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- May 15, 2023 13:30
- Sampling point
- TF102 Treatement Facility TF102
- Sample type
- Routine
- Lab sample
- IN-230516-014
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Barium 1010 EPA method 200.8
- Result
- 0.0019 mg/l
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Chromium 1020 EPA method 200.8
- Result
- 0.0008 mg/l
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.151 mg/l
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2021 – Dec 31, 2023
-
- Collected
- Dec 5, 2022 12:30
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- IN-221206-010
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.0036 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.171 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
- Collected
- Dec 5, 2022 12:30
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- HA-221206-013
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Total Haloacetic Acids (Haa5) 2456 EPA method 552.2
- Result
- 9.58 ug/l
Routine (10).