Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Chemical and radiological sample results

MS0670010 , Rome Water System

17 of the 57 analytes this system has been tested for have been detected at least once, across 96 samples on record.

The other 40 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 96 samples on record, detections range from October 27, 2003 to April 2, 2025. These figures cover the whole record.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for Rome Water System, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Copper, Free 1022 Inorganic Chemical 30 of 30 results Jul 10, 2007 Aug 7, 2023
Lead 1030 Inorganic Chemical 17 of 30 results Jul 10, 2007 Aug 7, 2023
Barium 1010 Inorganic Chemical 10 of 10 results Oct 27, 2003 Apr 2, 2025
Fluoride 1025 Inorganic Chemical 10 of 10 results Oct 27, 2003 Apr 2, 2025
Chromium 1020 Inorganic Chemical 7 of 10 results Oct 27, 2003 Dec 6, 2022
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 5 of 7 results Jul 7, 2010 Feb 26, 2025
TTHM 2950 Organic Chemical 4 of 7 results Sep 12, 2007 Feb 26, 2025
Nickel 1036 Inorganic Chemical 2 of 10 results Jun 3, 2013 Dec 6, 2022
Dichloroacetic Acid 2451 Organic Chemical 2 of 4 results Oct 29, 2013 Aug 25, 2016
Chloroform 2941 Organic Chemical 2 of 4 results Sep 12, 2007 Oct 29, 2013
Gross Alpha Particle Activity 4109 Radionuclide 2 of 4 results Jun 27, 2012 Sep 19, 2012
Selenium 1045 Inorganic Chemical 2 of 10 results Apr 27, 2005 Apr 12, 2006
Nitrate-Nitrite 1038 Inorganic Chemical 1 of 21 results Apr 4, 2018 Apr 4, 2018
Nitrite 1041 Inorganic Chemical 1 of 21 results Apr 4, 2018 Apr 4, 2018
Bromoform 2942 Organic Chemical 1 of 4 results Sep 12, 2007 Sep 12, 2007
Bromodichloromethane 2943 Organic Chemical 1 of 4 results Sep 12, 2007 Sep 12, 2007
Dibromochloromethane 2944 Organic Chemical 1 of 4 results Sep 12, 2007 Sep 12, 2007

No date range is applied: this list draws on every sample on record. Show the last two years only.

The most recent samples, result by result

The table below lists 61–70 of 96 samples, newest first — collected June 1, 2009 to June 22, 2011. The summary above covers all 96.

57 results from the 10 samples listed here: 7 detected, 50 not detected. Across the whole record it is 98 of 436. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for Rome Water System, every result from 61 to 70 of 96 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Jun 22, 2011
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
110623-062PB
Laboratory
MSDH Lab
0.1589 mg/l , sample collected Jun 22, 2011, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 22, 2011, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Collected
Jun 22, 2011
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
110623-061PB
Laboratory
MSDH Lab
0.1651 mg/l , sample collected Jun 22, 2011, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 22, 2011, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Collected
Mar 28, 2011
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
110329-045NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Mar 28, 2011, sampling point TF101 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Mar 28, 2011, sampling point TF101 Nitrate 1040 EPA method 353.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Mar 28, 2011, sampling point TF101 Nitrite 1041 EPA method 353.2 Jan 1, 2011 – Dec 31, 2011
Collected
Sep 23, 2010
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
100924-009VO
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 1,2,4-Trichlorobenzene 2378 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Cis-1,2-Dichloroethylene 2380 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Xylenes, Total 2955 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Dichloromethane 2964 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 O-Dichlorobenzene 2968 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 P-Dichlorobenzene 2969 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Vinyl Chloride 2976 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 1,1-Dichloroethylene 2977 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Trans-1,2-Dichloroethylene 2979 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 1,2-Dichloroethane 2980 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 1,1,1-Trichloroethane 2981 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Carbon Tetrachloride 2982 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 1,2-Dichloropropane 2983 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Trichloroethylene 2984 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 1,1,2-Trichloroethane 2985 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Tetrachloroethylene 2987 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Chlorobenzene 2989 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Benzene 2990 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Toluene 2991 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Ethylbenzene 2992 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 23, 2010, sampling point TF101 Styrene 2996 EPA method 524.2 Jan 1, 2005 – Dec 31, 2010
Collected
Sep 20, 2010
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
100921-005NI
Laboratory
MSDH Lab
Not detected below 0.25 mg/l Minimum Reporting Level , sample collected Sep 20, 2010, sampling point TF101 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2010 – Dec 31, 2010
Not detected below 0.2 mg/l Minimum Reporting Level , sample collected Sep 20, 2010, sampling point TF101 Nitrate 1040 EPA method 353.2 Jan 1, 2010 – Dec 31, 2010
Not detected below 0.05 mg/l Minimum Reporting Level , sample collected Sep 20, 2010, sampling point TF101 Nitrite 1041 EPA method 353.2 Jan 1, 2010 – Dec 31, 2010
Collected
Jul 7, 2010
Sampling point
MRT000 Max. Res. Time
Sample type
Routine
Lab sample
100708-001TH
Laboratory
MSDH Lab
Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Chloroform 2941 EPA method 524.2 Not recorded
Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Bromoform 2942 EPA method 524.2 Not recorded
Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Bromodichloromethane 2943 EPA method 524.2 Not recorded
Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Dibromochloromethane 2944 EPA method 524.2 Not recorded
0 This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. The agency recorded a value but no unit of measure for it. The unit is NOT inferable from the analyte: many analytes are reported in more than one unit — TTHM and HAA5 in both MG/L and UG/L — so there is no per-analyte default to fall back on. The number is published as it stands and must not be compared to a limit. The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Jul 7, 2010, sampling point MRT000 TTHM 2950 EPA method 524.2 Jan 1, 2008 – Dec 31, 2010
Collected
Jul 7, 2010
Sampling point
MRT000 Max. Res. Time
Sample type
Routine
Lab sample
100708-001HA
Laboratory
MSDH Lab
Not detected below 0.002 mg/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Monochloroacetic Acid 2450 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Dichloroacetic Acid 2451 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Trichloroacetic Acid 2452 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Monobromoacetic Acid 2453 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jul 7, 2010, sampling point MRT000 Dibromoacetic Acid 2454 EPA method 552.2 Not recorded
0 This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. The agency recorded a value but no unit of measure for it. The unit is NOT inferable from the analyte: many analytes are reported in more than one unit — TTHM and HAA5 in both MG/L and UG/L — so there is no per-analyte default to fall back on. The number is published as it stands and must not be compared to a limit. The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Jul 7, 2010, sampling point MRT000 Total Haloacetic Acids (Haa5) 2456 Jan 1, 2008 – Dec 31, 2010
Collected
Mar 29, 2010
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
100330-025CN
Laboratory
MSDH Lab
Not detected below 15 ug/l Minimum Reporting Level , sample collected Mar 29, 2010, sampling point TF101 Cyanide 1024 EPA method QC10204001X Jan 1, 2008 – Dec 31, 2010
Collected
Feb 10, 2010
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
100211-051IN
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF101 Arsenic 1005 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
0.042492 mg/l , sample collected Feb 10, 2010, sampling point TF101 Barium 1010 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF101 Cadmium 1015 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
0.003134 mg/l , sample collected Feb 10, 2010, sampling point TF101 Chromium 1020 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
0.199 mg/l , sample collected Feb 10, 2010, sampling point TF101 Fluoride 1025 EPA method 380-75WE Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF101 Mercury 1035 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF101 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF101 Selenium 1045 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF101 Antimony, Total 1074 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF101 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF101 Thallium, Total 1085 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Collected
Jun 1, 2009
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
090602-006NI
Laboratory
MSDH Lab
Not detected below 0.25 mg/l Minimum Reporting Level , sample collected Jun 1, 2009, sampling point TF101 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2009 – Dec 31, 2009
Not detected below 0.2 mg/l Minimum Reporting Level , sample collected Jun 1, 2009, sampling point TF101 Nitrate 1040 EPA method 353.2 Jan 1, 2009 – Dec 31, 2009
Not detected below 0.05 mg/l Minimum Reporting Level , sample collected Jun 1, 2009, sampling point TF101 Nitrite 1041 EPA method 353.2 Jan 1, 2009 – Dec 31, 2009

Routine (10).