This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0670014 , MS State Penitentiary-MN Ln
29 of the 57 analytes this system has been tested for have been detected at least once, across 692 samples on record.
The other 28 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 692 samples on record, detections range from October 27, 2003 to April 6, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 390 of 392 results | Jun 3, 2004 | Sep 28, 2025 |
| Lead 1030 | Inorganic Chemical | 280 of 392 results | Jun 3, 2004 | Sep 28, 2025 |
| TTHM 2950 | Organic Chemical | 40 of 41 results | Aug 16, 2004 | Oct 28, 2024 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 37 of 42 results | Sep 13, 2007 | Apr 6, 2026 |
| Barium 1010 | Inorganic Chemical | 37 of 37 results | Oct 27, 2003 | May 5, 2025 |
| Fluoride 1025 | Inorganic Chemical | 37 of 37 results | Oct 27, 2003 | May 5, 2025 |
| Chromium 1020 | Inorganic Chemical | 29 of 37 results | Oct 27, 2003 | May 5, 2025 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 20 of 21 results | Mar 29, 2012 | Oct 23, 2012 |
| Chloroform 2941 | Organic Chemical | 16 of 16 results | Oct 3, 2007 | May 28, 2024 |
| Bromodichloromethane 2943 | Organic Chemical | 15 of 16 results | Oct 3, 2007 | May 28, 2024 |
| Dichloroacetic Acid 2451 | Organic Chemical | 14 of 16 results | Jun 4, 2008 | Apr 6, 2026 |
| Trichloroacetic Acid 2452 | Organic Chemical | 14 of 16 results | Jun 4, 2008 | Apr 6, 2026 |
| Dibromochloromethane 2944 | Organic Chemical | 14 of 16 results | Oct 3, 2007 | May 28, 2024 |
| Selenium 1045 | Inorganic Chemical | 13 of 37 results | Apr 26, 2005 | May 5, 2025 |
| Dibromoacetic Acid 2454 | Organic Chemical | 11 of 16 results | Sep 4, 2008 | Apr 6, 2026 |
| Arsenic 1005 | Inorganic Chemical | 10 of 37 results | Apr 26, 2005 | May 5, 2025 |
| Nickel 1036 | Inorganic Chemical | 10 of 37 results | Apr 26, 2005 | May 5, 2025 |
| Bromoform 2942 | Organic Chemical | 6 of 16 results | Sep 4, 2008 | Dec 19, 2017 |
| Monobromoacetic Acid 2453 | Organic Chemical | 4 of 16 results | Jun 17, 2009 | Apr 6, 2026 |
| Sodium 1052 | Inorganic Chemical | 4 of 4 results | Dec 11, 2023 | Dec 11, 2023 |
| Monochloroacetic Acid 2450 | Organic Chemical | 4 of 16 results | Jun 17, 2009 | Nov 28, 2017 |
| Cadmium 1015 | Inorganic Chemical | 3 of 37 results | Apr 26, 2005 | Apr 26, 2005 |
| Mercury 1035 | Inorganic Chemical | 2 of 33 results | Apr 26, 2005 | Apr 26, 2005 |
| Thallium, Total 1085 | Inorganic Chemical | 2 of 37 results | Apr 26, 2005 | Apr 26, 2005 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 1 of 21 results | Apr 6, 2020 | Apr 6, 2020 |
| Radium-226 4020 | Radionuclide | 1 of 21 results | Apr 6, 2020 | Apr 6, 2020 |
| Radium-228 4030 | Radionuclide | 1 of 21 results | Apr 6, 2020 | Apr 6, 2020 |
| Cyanide 1024 | Inorganic Chemical | 1 of 36 results | Sep 11, 2013 | Sep 11, 2013 |
| Beryllium, Total 1075 | Inorganic Chemical | 1 of 37 results | Apr 26, 2005 | Apr 26, 2005 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 671–680 of 692 samples, newest first — collected March 31, 2004 to June 3, 2004. The summary above covers all 692.
56 results from the 10 samples listed here: 12 detected, 44 not detected. Across the whole record it is 1,017 of 2,369. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0876 mg/l , sample collected Jun 3, 2004, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2004 – Jun 30, 2004 |
| 0.0009 mg/l , sample collected Jun 3, 2004, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2004 – Jun 30, 2004 |
|
||
| 0.0043 mg/l , sample collected Jun 3, 2004, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2004 – Jun 30, 2004 |
| 0.0014 mg/l , sample collected Jun 3, 2004, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2004 – Jun 30, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.003 mg/l , sample collected Mar 31, 2004, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.349 mg/l , sample collected Mar 31, 2004, sampling point TF102 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.006 mg/l , sample collected Mar 31, 2004, sampling point TF107 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.397 mg/l , sample collected Mar 31, 2004, sampling point TF107 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.007 mg/l , sample collected Mar 31, 2004, sampling point TF104 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.395 mg/l , sample collected Mar 31, 2004, sampling point TF104 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.006 mg/l , sample collected Mar 31, 2004, sampling point TF105 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.346 mg/l , sample collected Mar 31, 2004, sampling point TF105 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF104 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF107 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Mar 31, 2004, sampling point TF105 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
-
- Collected
- Jun 3, 2004
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 040604-065PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Jun 30, 2004
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0876 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0009 mg/l
-
- Collected
- Jun 3, 2004
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 040604-064PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Jun 30, 2004
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0043 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0014 mg/l
-
- Collected
- Mar 31, 2004
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 040401-053IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.003 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- 0.349 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Mar 31, 2004
- Sampling point
- TF107 Treatment Plant T107
- Sample type
- Routine
- Lab sample
- 040401-052IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.006 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- 0.397 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Mar 31, 2004
- Sampling point
- TF104 Treatment Plant T104
- Sample type
- Routine
- Lab sample
- 040401-051IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.007 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- 0.395 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Mar 31, 2004
- Sampling point
- TF105 Treatment Plant T105
- Sample type
- Routine
- Lab sample
- 040401-050IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.006 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- 0.346 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Mar 31, 2004
- Sampling point
- TF104 Treatment Plant T104
- Sample type
- Routine
- Lab sample
- 040401-011CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Mar 31, 2004
- Sampling point
- TF107 Treatment Plant T107
- Sample type
- Routine
- Lab sample
- 040401-010CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Mar 31, 2004
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 040401-009CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Mar 31, 2004
- Sampling point
- TF105 Treatment Plant T105
- Sample type
- Routine
- Lab sample
- 040401-008CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
Routine (10).