Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Chemical and radiological sample results

MS0710006 , City of Iuka

15 of the 58 analytes this system has been tested for have been detected at least once, across 157 samples on record.

The other 43 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 157 samples on record, detections range from October 29, 2003 to September 9, 2025. These figures cover the whole record; the list of samples further down is narrowed.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for City of Iuka, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Copper, Free 1022 Inorganic Chemical 70 of 70 results Aug 16, 2007 Sep 9, 2025
Lead 1030 Inorganic Chemical 27 of 70 results Aug 16, 2007 Jul 20, 2022
Nitrate-Nitrite 1038 Inorganic Chemical 18 of 21 results Jun 14, 2004 Apr 14, 2025
Nitrate 1040 Inorganic Chemical 18 of 21 results Jun 14, 2004 Apr 14, 2025
Barium 1010 Inorganic Chemical 10 of 10 results Oct 29, 2003 Apr 1, 2025
Nickel 1036 Inorganic Chemical 10 of 10 results Oct 29, 2003 Apr 1, 2025
Chromium 1020 Inorganic Chemical 6 of 10 results May 2, 2005 Apr 1, 2025
Gross Alpha, Incl. Radon & U 4002 Radionuclide 5 of 5 results Mar 14, 2012 Oct 9, 2012
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 3 of 17 results Jul 15, 2010 Oct 18, 2022
Fluoride 1025 Inorganic Chemical 2 of 10 results May 22, 2013 Apr 1, 2025
Sodium 1052 Inorganic Chemical 2 of 2 results Oct 3, 2019 Mar 28, 2023
TTHM 2950 Organic Chemical 2 of 12 results Sep 19, 2007 Jul 15, 2010
Selenium 1045 Inorganic Chemical 2 of 10 results May 2, 2005 Mar 3, 2010
Monobromoacetic Acid 2453 Organic Chemical 1 of 12 results Oct 27, 2020 Oct 27, 2020
Cadmium 1015 Inorganic Chemical 1 of 10 results May 2, 2005 May 2, 2005

Showing samples collected between September 25, 2024 and September 25, 2026. That is this page’s default, not a limit on what the agency records.

Show every sample on record

Choose a date range

The most recent samples, result by result

The table below lists 21–21 of 21 samples, newest first — collected April 1, 2025 to April 1, 2025. The summary above covers all 21.

10 results from the 1 sample listed here: 4 detected, 6 not detected. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for City of Iuka, every result from 21 to 21 of 21 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Apr 1, 2025 14:15
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
IN-250402-063
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2025 14:15, sampling point TF080 Arsenic 1005 EPA method 200.8 Jan 1, 2023 – Dec 31, 2025
0.0104 mg/l , sample collected Apr 1, 2025 14:15, sampling point TF080 Barium 1010 EPA method 200.8 Jan 1, 2023 – Dec 31, 2025
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2025 14:15, sampling point TF080 Cadmium 1015 EPA method 200.8 Jan 1, 2023 – Dec 31, 2025
0.0017 mg/l , sample collected Apr 1, 2025 14:15, sampling point TF080 Chromium 1020 EPA method 200.8 Jan 1, 2023 – Dec 31, 2025
0.102 mg/l , sample collected Apr 1, 2025 14:15, sampling point TF080 Fluoride 1025 EPA method QC 10-109-12-2-A Jan 1, 2023 – Dec 31, 2025
0.0034 mg/l , sample collected Apr 1, 2025 14:15, sampling point TF080 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Apr 1, 2025 14:15, sampling point TF080 Selenium 1045 EPA method 200.8 Jan 1, 2023 – Dec 31, 2025
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2025 14:15, sampling point TF080 Antimony, Total 1074 EPA method 200.8 Jan 1, 2023 – Dec 31, 2025
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2025 14:15, sampling point TF080 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2023 – Dec 31, 2025
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2025 14:15, sampling point TF080 Thallium, Total 1085 EPA method 200.8 Jan 1, 2023 – Dec 31, 2025

Routine (1).