This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0790007 , Town of Woodville
37 of the 74 analytes this system has been tested for have been detected at least once, across 205 samples on record.
The other 37 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 205 samples on record, detections range from November 3, 2003 to July 29, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 109 of 110 results | Sep 20, 2007 | Sep 9, 2025 |
| Lead 1030 | Inorganic Chemical | 59 of 110 results | Sep 20, 2007 | Sep 9, 2025 |
| TTHM 2950 | Organic Chemical | 14 of 19 results | Aug 30, 2004 | Feb 19, 2026 |
| Barium 1010 | Inorganic Chemical | 12 of 12 results | Nov 3, 2003 | Jul 29, 2026 |
| Chloroform 2941 | Organic Chemical | 11 of 15 results | Sep 17, 2007 | Feb 19, 2026 |
| Bromodichloromethane 2943 | Organic Chemical | 9 of 15 results | Sep 12, 2016 | Feb 19, 2026 |
| Fluoride 1025 | Inorganic Chemical | 8 of 14 results | Nov 3, 2003 | Jul 29, 2026 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 8 of 21 results | Aug 3, 2010 | Jun 10, 2025 |
| Dibromochloromethane 2944 | Organic Chemical | 5 of 15 results | Nov 20, 2024 | Feb 19, 2026 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 5 results | Dec 12, 2011 | Jul 17, 2012 |
| Chromium 1020 | Inorganic Chemical | 5 of 12 results | Nov 3, 2003 | Apr 25, 2011 |
| Sodium 1052 | Inorganic Chemical | 4 of 4 results | Jan 24, 2006 | Jul 29, 2026 |
| Dichloroacetic Acid 2451 | Organic Chemical | 4 of 16 results | Sep 17, 2013 | Jun 10, 2025 |
| Sulfate 1055 | Inorganic Chemical | 4 of 4 results | Nov 3, 2003 | Jan 9, 2018 |
| Nickel 1036 | Inorganic Chemical | 4 of 11 results | May 2, 2005 | Mar 31, 2014 |
| Trichloroacetic Acid 2452 | Organic Chemical | 2 of 16 results | Sep 12, 2016 | Jun 10, 2025 |
| Monobromoacetic Acid 2453 | Organic Chemical | 2 of 16 results | Aug 3, 2010 | Oct 26, 2020 |
| Calcium 1016 | Inorganic Chemical | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Iron 1028 | Inorganic Chemical | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Magnesium 1031 | Inorganic Chemical | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Manganese 1032 | Inorganic Chemical | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Potassium 1042 | Inorganic Chemical | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Residue, Total, Filterable 1057 | Water Quality | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Carbon Dioxide 1901 | Water Quality | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Hardness, Total (As Caco3) 1915 | Water Quality | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Alkalinity, Total 1927 | Water Quality | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Iron, Field Result FEFD | Inorganic Chemical | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Calculated Sodium NACA | Water Quality | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| PH, Field Result PHFD | Water Quality | 2 of 2 results | Jan 24, 2006 | Jan 9, 2018 |
| Selenium 1045 | Inorganic Chemical | 2 of 12 results | May 2, 2005 | Dec 4, 2006 |
| Mercury 1035 | Inorganic Chemical | 1 of 12 results | Jul 29, 2026 | Jul 29, 2026 |
| Color 1905 | Water Quality | 1 of 1 result | Jan 9, 2018 | Jan 9, 2018 |
| Arsenic 1005 | Inorganic Chemical | 1 of 12 results | Dec 4, 2006 | Dec 4, 2006 |
| Alkalinity, Caco3 Stability 1067 | Water Quality | 1 of 1 result | Jan 24, 2006 | Jan 24, 2006 |
| PH 1925 | Water Quality | 1 of 1 result | Jan 24, 2006 | Jan 24, 2006 |
| Temperature, Field Result TEMP | Water Quality | 1 of 1 result | Jan 24, 2006 | Jan 24, 2006 |
| Cadmium 1015 | Inorganic Chemical | 1 of 12 results | May 2, 2005 | May 2, 2005 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 151–160 of 205 samples, newest first — collected July 30, 2008 to August 26, 2010. The summary above covers all 205.
29 results from the 10 samples listed here: 14 detected, 15 not detected. Across the whole record it is 298 of 884. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0473 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0034 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.0392 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 26, 2010, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.2442 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0024 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.1143 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0013 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.043 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.004 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.0475 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0011 mg/l , sample collected Aug 26, 2010, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 0.002 mg/l Minimum Reporting Level , sample collected Aug 3, 2010, sampling point MRT000 | Monochloroacetic Acid 2450 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Aug 3, 2010, sampling point MRT000 | Dichloroacetic Acid 2451 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Aug 3, 2010, sampling point MRT000 | Trichloroacetic Acid 2452 EPA method 552.2 | Not recorded |
| 0.002 mg/l , sample collected Aug 3, 2010, sampling point MRT000 | Monobromoacetic Acid 2453 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Aug 3, 2010, sampling point MRT000 | Dibromoacetic Acid 2454 EPA method 552.2 | Not recorded |
| 0 mg/l This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. , sample collected Aug 3, 2010, sampling point MRT000 | Total Haloacetic Acids (Haa5) 2456 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 3, 2010, sampling point MRT000 | Chloroform 2941 EPA method 524.2 | Not recorded |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 3, 2010, sampling point MRT000 | Bromoform 2942 EPA method 524.2 | Not recorded |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 3, 2010, sampling point MRT000 | Bromodichloromethane 2943 EPA method 524.2 | Not recorded |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 3, 2010, sampling point MRT000 | Dibromochloromethane 2944 EPA method 524.2 | Not recorded |
| 0 This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. The agency recorded a value but no unit of measure for it. The unit is NOT inferable from the analyte: many analytes are reported in more than one unit — TTHM and HAA5 in both MG/L and UG/L — so there is no per-analyte default to fall back on. The number is published as it stands and must not be compared to a limit. The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Aug 3, 2010, sampling point MRT000 | TTHM 2950 EPA method 524.2 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 0.25 mg/l Minimum Reporting Level , sample collected Jun 8, 2009, sampling point TF081 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.2 mg/l Minimum Reporting Level , sample collected Jun 8, 2009, sampling point TF081 | Nitrate 1040 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected Jun 8, 2009, sampling point TF081 | Nitrite 1041 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jul 30, 2008, sampling point TF081 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2008 – Dec 31, 2008 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jul 30, 2008, sampling point TF081 | Nitrate 1040 EPA method 353.2 | Jan 1, 2008 – Dec 31, 2008 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jul 30, 2008, sampling point TF081 | Nitrite 1041 EPA method 353.2 | Jan 1, 2008 – Dec 31, 2008 |
-
- Collected
- Aug 26, 2010
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 100827-036PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0473 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0034 mg/l
-
- Collected
- Aug 26, 2010
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 100827-035PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0392 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Aug 26, 2010
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 100827-034PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.2442 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0024 mg/l
-
- Collected
- Aug 26, 2010
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 100827-033PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.1143 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0013 mg/l
-
- Collected
- Aug 26, 2010
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 100827-032PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.043 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.004 mg/l
-
- Collected
- Aug 26, 2010
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 100827-031PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0475 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0011 mg/l
-
- Collected
- Aug 3, 2010
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- 100804-008HA
- Laboratory
- MSDH Lab
-
Monochloroacetic Acid 2450 EPA method 552.2
- Result
- Not detected below 0.002 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Dichloroacetic Acid 2451 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Trichloroacetic Acid 2452 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Monobromoacetic Acid 2453 EPA method 552.2
- Result
- 0.002 mg/l
- Monitoring period
- Not recorded
-
Dibromoacetic Acid 2454 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Total Haloacetic Acids (Haa5) 2456
- Result
- 0 mg/l This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here.
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Aug 3, 2010
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- 100804-008TH
- Laboratory
- MSDH Lab
-
Chloroform 2941 EPA method 524.2
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Bromoform 2942 EPA method 524.2
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Bromodichloromethane 2943 EPA method 524.2
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Dibromochloromethane 2944 EPA method 524.2
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
TTHM 2950 EPA method 524.2
- Result
- 0 This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. The agency recorded a value but no unit of measure for it. The unit is NOT inferable from the analyte: many analytes are reported in more than one unit — TTHM and HAA5 in both MG/L and UG/L — so there is no per-analyte default to fall back on. The number is published as it stands and must not be compared to a limit. The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Jun 8, 2009
- Sampling point
- TF081 1ST West St
- Sample type
- Routine
- Lab sample
- 090609-083NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2009 – Dec 31, 2009
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.25 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.2 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
-
- Collected
- Jul 30, 2008
- Sampling point
- TF081 1ST West St
- Sample type
- Routine
- Lab sample
- 080731-049NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2008
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
Routine (10).