Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0790033 , Wilkinson Co Correctional Cent

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for Wilkinson Co Correctional Cent, 24 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2022 – Dec 31, 2024 10 0.371 mg/l DS000 Accepted
Lead Jan 1, 2022 – Dec 31, 2024 10 0 mg/l DS000 Accepted
Copper Jan 1, 2019 – Dec 31, 2021 10 0.65 mg/l DS000 Accepted
Lead Jan 1, 2019 – Dec 31, 2021 10 0.0015 mg/l DS000 Accepted
Copper Jan 1, 2016 – Dec 31, 2018 10 0.6281 mg/l DS000 Accepted
Lead Jan 1, 2016 – Dec 31, 2018 10 0.0018 mg/l DS000 Accepted
Copper Jan 1, 2013 – Dec 31, 2015 10 0.5233 mg/l DS000 Accepted
Lead Jan 1, 2013 – Dec 31, 2015 10 0.0011 mg/l DS000 Accepted
Copper Jan 1, 2010 – Dec 31, 2012 10 0.8468 mg/l DS000 Accepted
Lead Jan 1, 2010 – Dec 31, 2012 10 0.0015 mg/l DS000 Accepted
Copper Jan 1, 2009 – Dec 31, 2009 10 0.0114 mg/l DS000 Accepted
Lead Jan 1, 2009 – Dec 31, 2009 10 0 mg/l DS000 Accepted
Copper Jan 1, 2008 – Dec 31, 2008 10 0.0677 mg/l DS000 Accepted
Lead Jan 1, 2008 – Dec 31, 2008 10 0 mg/l DS000 Accepted
Copper Jan 1, 2007 – Dec 31, 2007 10 0.0036 mg/l DS000 Accepted
Lead Jan 1, 2007 – Dec 31, 2007 10 0 mg/l DS000 Accepted
Copper Jan 1, 2004 – Dec 31, 2004 10 0.0087 mg/l DS000 Accepted
Lead Jan 1, 2004 – Dec 31, 2004 10 0 mg/l DS000 Accepted
Copper Jul 1, 2003 – Dec 31, 2003 20 0 mg/l DS000 Accepted
Lead Jul 1, 2003 – Dec 31, 2003 20 0 mg/l DS000 Accepted
Copper Jan 1, 2003 – Jun 30, 2003 20 0.007 mg/l DS000 Accepted
Lead Jan 1, 2003 – Jun 30, 2003 20 0 mg/l DS000 Accepted
Copper Jul 1, 2000 – Dec 31, 2000 5 0.01 mg/l DS000 Accepted
Lead Jul 1, 2000 – Dec 31, 2000 5 0 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.