Chemical and radiological sample results

MS0820011 , Renshaw Water Association

31 of the 72 analytes this system has been tested for have been detected at least once, across 108 samples on record.

The other 41 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 108 samples on record, detections range from November 5, 2003 to April 7, 2025. These figures cover the whole record.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for Renshaw Water Association, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Copper, Free 1022 Inorganic Chemical 31 of 31 results Jul 11, 2007 Aug 21, 2023
Lead 1030 Inorganic Chemical 31 of 31 results Jul 11, 2007 Aug 21, 2023
Barium 1010 Inorganic Chemical 10 of 10 results Nov 5, 2003 Apr 7, 2025
TTHM 2950 Organic Chemical 6 of 8 results Sep 1, 2004 Dec 6, 2022
Fluoride 1025 Inorganic Chemical 5 of 11 results Apr 12, 2004 Apr 7, 2025
Nickel 1036 Inorganic Chemical 5 of 10 results May 12, 2010 Apr 7, 2025
Gross Alpha, Incl. Radon & U 4002 Radionuclide 5 of 5 results Dec 6, 2011 Jul 17, 2012
Chromium 1020 Inorganic Chemical 4 of 10 results Apr 12, 2004 Apr 7, 2025
Sodium 1052 Inorganic Chemical 3 of 3 results Sep 17, 2019 Mar 21, 2023
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 3 of 7 results Aug 2, 2010 Dec 6, 2022
Sulfate 1055 Inorganic Chemical 3 of 3 results Nov 5, 2003 Sep 24, 2020
Chloroform 2941 Organic Chemical 3 of 4 results Sep 26, 2007 Sep 17, 2013
Bromodichloromethane 2943 Organic Chemical 3 of 4 results Sep 26, 2007 Sep 17, 2013
Dibromochloromethane 2944 Organic Chemical 2 of 4 results Sep 26, 2007 Aug 2, 2010
Calcium 1016 Inorganic Chemical 1 of 1 result Sep 24, 2020 Sep 24, 2020
Iron 1028 Inorganic Chemical 1 of 1 result Sep 24, 2020 Sep 24, 2020
Magnesium 1031 Inorganic Chemical 1 of 1 result Sep 24, 2020 Sep 24, 2020
Manganese 1032 Inorganic Chemical 1 of 1 result Sep 24, 2020 Sep 24, 2020
Potassium 1042 Inorganic Chemical 1 of 1 result Sep 24, 2020 Sep 24, 2020
Residue, Total, Filterable 1057 Water Quality 1 of 1 result Sep 24, 2020 Sep 24, 2020
Alkalinity, Caco3 Stability 1067 Water Quality 1 of 1 result Sep 24, 2020 Sep 24, 2020
Carbon Dioxide 1901 Water Quality 1 of 1 result Sep 24, 2020 Sep 24, 2020
Color 1905 Water Quality 1 of 1 result Sep 24, 2020 Sep 24, 2020
Hardness, Total (As Caco3) 1915 Water Quality 1 of 1 result Sep 24, 2020 Sep 24, 2020
Alkalinity, Total 1927 Water Quality 1 of 1 result Sep 24, 2020 Sep 24, 2020
Iron, Field Result FEFD Inorganic Chemical 1 of 1 result Sep 24, 2020 Sep 24, 2020
Calculated Sodium NACA Water Quality 1 of 1 result Sep 24, 2020 Sep 24, 2020
PH, Field Result PHFD Water Quality 1 of 1 result Sep 24, 2020 Sep 24, 2020
Dichloroacetic Acid 2451 Organic Chemical 1 of 3 results Sep 17, 2013 Sep 17, 2013
Nitrate 1040 Inorganic Chemical 1 of 21 results Jul 23, 2007 Jul 23, 2007
Selenium 1045 Inorganic Chemical 1 of 10 results Apr 12, 2004 Apr 12, 2004

No date range is applied: this list draws on every sample on record. Show the last two years only.

The most recent samples, result by result

The table below lists 91–100 of 108 samples, newest first — collected September 1, 2004 to July 11, 2007. The summary above covers all 108.

76 results from the 10 samples listed here: 5 detected, 71 not detected. Across the whole record it is 131 of 486. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for Renshaw Water Association, every result from 91 to 100 of 108 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Jul 11, 2007
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
070712-065PB
Laboratory
MSDH Lab
0.0995 mg/l , sample collected Jul 11, 2007, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
0.0042 mg/l , sample collected Jul 11, 2007, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
Collected
Aug 14, 2006
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
060815-009NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Aug 14, 2006, sampling point TF102 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2006 – Dec 31, 2006
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Aug 14, 2006, sampling point TF102 Nitrate 1040 EPA method 353.2 Jan 1, 2006 – Dec 31, 2006
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Aug 14, 2006, sampling point TF102 Nitrite 1041 EPA method 353.2 Jan 1, 2006 – Dec 31, 2006
Collected
Apr 18, 2006
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
060419-057IN
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Arsenic 1005 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
0.020332 mg/l , sample collected Apr 18, 2006, sampling point TF102 Barium 1010 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Cadmium 1015 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Chromium 1020 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
0.110237 mg/l , sample collected Apr 18, 2006, sampling point TF102 Fluoride 1025 EPA method 380-75WE Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0002 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Mercury 1035 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Selenium 1045 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Antimony, Total 1074 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Thallium, Total 1085 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2006, sampling point TF102 Uranium-238 4009 Not recorded
Collected
Apr 17, 2006
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
060418-071CN
Laboratory
MSDH Lab
Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Apr 17, 2006, sampling point TF102 Cyanide 1024 EPA method QC10204001X Jan 1, 2005 – Dec 31, 2007
Collected
Oct 4, 2005
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
051005-002NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Oct 4, 2005, sampling point TF102 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2005 – Dec 31, 2005
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Oct 4, 2005, sampling point TF102 Nitrate 1040 EPA method 353.2 Jan 1, 2005 – Dec 31, 2005
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Oct 4, 2005, sampling point TF102 Nitrite 1041 EPA method 353.2 Jan 1, 2005 – Dec 31, 2005
Collected
May 4, 2005
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
050505-055CN
Laboratory
MSDH Lab
Not detected below 0.005 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Cyanide 1024 EPA method QC10204001X Jan 1, 2005 – Dec 31, 2007
Collected
May 4, 2005
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
050505-056IN
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Arsenic 1005 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
0.021892 mg/l , sample collected May 4, 2005, sampling point TF102 Barium 1010 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Cadmium 1015 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Chromium 1020 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Fluoride 1025 EPA method 380-75WE Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0002 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Mercury 1035 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Selenium 1045 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Antimony, Total 1074 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 4, 2005, sampling point TF102 Thallium, Total 1085 EPA method 200.8 Jan 1, 2005 – Dec 31, 2007
Collected
Dec 15, 2004
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
041216-034VO
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 1,2,4-Trichlorobenzene 2378 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Cis-1,2-Dichloroethylene 2380 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Xylenes, Total 2955 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Dichloromethane 2964 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 O-Dichlorobenzene 2968 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 P-Dichlorobenzene 2969 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Vinyl Chloride 2976 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 1,1-Dichloroethylene 2977 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Trans-1,2-Dichloroethylene 2979 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 1,2-Dichloroethane 2980 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 1,1,1-Trichloroethane 2981 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Carbon Tetrachloride 2982 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 1,2-Dichloropropane 2983 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Trichloroethylene 2984 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 1,1,2-Trichloroethane 2985 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Tetrachloroethylene 2987 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Chlorobenzene 2989 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Benzene 2990 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Toluene 2991 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Ethylbenzene 2992 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Dec 15, 2004, sampling point TF102 Styrene 2996 EPA method 524.2 Oct 1, 2004 – Dec 31, 2004
Collected
Sep 14, 2004
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
040915-010VO
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 1,2,4-Trichlorobenzene 2378 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Cis-1,2-Dichloroethylene 2380 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Xylenes, Total 2955 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Dichloromethane 2964 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 O-Dichlorobenzene 2968 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 P-Dichlorobenzene 2969 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Vinyl Chloride 2976 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 1,1-Dichloroethylene 2977 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Trans-1,2-Dichloroethylene 2979 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 1,2-Dichloroethane 2980 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 1,1,1-Trichloroethane 2981 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Carbon Tetrachloride 2982 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 1,2-Dichloropropane 2983 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Trichloroethylene 2984 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 1,1,2-Trichloroethane 2985 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Tetrachloroethylene 2987 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Chlorobenzene 2989 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Benzene 2990 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Toluene 2991 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Ethylbenzene 2992 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Not detected below 0.0005 mg/l Method Detection Limit , sample collected Sep 14, 2004, sampling point TF102 Styrene 2996 EPA method 524.2 Jul 1, 2004 – Sep 30, 2004
Collected
Sep 1, 2004
Sampling point
MRT000 Max. Res. Time
Sample type
Routine
Lab sample
040902-030HA
Laboratory
MSDH Lab
Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Sep 1, 2004, sampling point MRT000 Total Haloacetic Acids (Haa5) 2456 EPA method 552.2 Jan 1, 2004 – Dec 31, 2004

Routine (10).