Chemical and radiological sample results
MS0070002 , Big Creek Water Association
23 of the 57 analytes this system has been tested for have been detected at least once, across 356 samples on record.
The other 34 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 356 samples on record, detections range from November 11, 1993 to July 31, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 129 of 147 results | Nov 11, 1993 | Jul 31, 2026 |
| Lead 1030 | Inorganic Chemical | 75 of 147 results | Nov 11, 1993 | Jun 22, 2022 |
| Fluoride 1025 | Inorganic Chemical | 44 of 44 results | Jun 25, 2002 | Jul 30, 2026 |
| Arsenic 1005 | Inorganic Chemical | 44 of 44 results | Jun 25, 2002 | Jun 11, 2026 |
| Barium 1010 | Inorganic Chemical | 44 of 44 results | Jun 25, 2002 | Jun 11, 2026 |
| Selenium 1045 | Inorganic Chemical | 37 of 44 results | Jun 25, 2002 | Jun 11, 2026 |
| Nickel 1036 | Inorganic Chemical | 37 of 43 results | Jun 25, 2002 | Oct 8, 2025 |
| Chromium 1020 | Inorganic Chemical | 31 of 44 results | Jun 25, 2002 | Oct 8, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 20 of 32 results | Jun 27, 2007 | Mar 26, 2025 |
| TTHM 2950 | Organic Chemical | 15 of 30 results | Jun 27, 2007 | Oct 11, 2023 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 12 of 12 results | Dec 8, 2011 | Mar 14, 2016 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 11 of 12 results | Dec 8, 2011 | Mar 14, 2016 |
| Radium-226 4020 | Radionuclide | 11 of 12 results | Dec 8, 2011 | Mar 14, 2016 |
| Nitrate 1040 | Inorganic Chemical | 9 of 43 results | May 3, 2004 | Mar 14, 2016 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 7 of 43 results | Jul 18, 2005 | Mar 14, 2016 |
| Sodium 1052 | Inorganic Chemical | 6 of 6 results | Sep 20, 2019 | Jun 11, 2026 |
| Radium-228 4030 | Radionuclide | 6 of 12 results | Dec 8, 2011 | Mar 14, 2016 |
| Nitrite 1041 | Inorganic Chemical | 6 of 43 results | Jul 18, 2005 | Jan 18, 2011 |
| Dibromoacetic Acid 2454 | Organic Chemical | 4 of 7 results | Aug 13, 2008 | Jun 4, 2019 |
| Bromoform 2942 | Organic Chemical | 3 of 8 results | Aug 4, 2014 | Sep 6, 2017 |
| Dichloroacetic Acid 2451 | Organic Chemical | 1 of 7 results | Jun 4, 2019 | Jun 4, 2019 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 7 results | Jun 4, 2019 | Jun 4, 2019 |
| Dibromochloromethane 2944 | Organic Chemical | 1 of 8 results | Aug 4, 2014 | Aug 4, 2014 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 121–130 of 356 samples, newest first — collected April 23, 2018 to June 15, 2019. The summary above covers all 356.
40 results from the 10 samples listed here: 16 detected, 24 not detected. Across the whole record it is 554 of 1,415. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.3572 mg/l , sample collected Jun 15, 2019 04:48, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 15, 2019 04:48, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
|
||
| Not detected below 0.002 mg/l Minimum Reporting Level , sample collected Jun 4, 2019 03:58, sampling point MRT000 | Monochloroacetic Acid 2450 EPA method 552.2 | Not recorded |
| 0.002 mg/l , sample collected Jun 4, 2019 03:58, sampling point MRT000 | Dichloroacetic Acid 2451 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jun 4, 2019 03:58, sampling point MRT000 | Trichloroacetic Acid 2452 EPA method 552.2 | Not recorded |
| 0.012 mg/l , sample collected Jun 4, 2019 03:58, sampling point MRT000 | Monobromoacetic Acid 2453 EPA method 552.2 | Not recorded |
| 0.005 mg/l , sample collected Jun 4, 2019 03:58, sampling point MRT000 | Dibromoacetic Acid 2454 EPA method 552.2 | Not recorded |
| 0.019 mg/l , sample collected Jun 4, 2019 03:58, sampling point MRT000 | Total Haloacetic Acids (Haa5) 2456 | Jan 1, 2019 – Dec 31, 2019 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jan 29, 2019 15:09, sampling point TF102 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jan 29, 2019 15:09, sampling point TF102 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jan 29, 2019 15:09, sampling point TF102 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jan 29, 2019 14:48, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jan 29, 2019 14:48, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jan 29, 2019 14:48, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
|
||
| 0.0047 mg/l , sample collected Sep 17, 2018 02:11, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.1112 mg/l , sample collected Sep 17, 2018 02:11, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:11, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0035 mg/l , sample collected Sep 17, 2018 02:11, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.443 mg/l , sample collected Sep 17, 2018 02:11, sampling point TF102 | Fluoride 1025 EPA method 300.0 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:11, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:11, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.0026 mg/l , sample collected Sep 17, 2018 02:11, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:11, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:11, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:11, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
|
||
| 0.0106 mg/l , sample collected Sep 17, 2018 02:35, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.1463 mg/l , sample collected Sep 17, 2018 02:35, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:35, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0042 mg/l , sample collected Sep 17, 2018 02:35, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.434 mg/l , sample collected Sep 17, 2018 02:35, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:35, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0006 mg/l , sample collected Sep 17, 2018 02:35, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.0041 mg/l , sample collected Sep 17, 2018 02:35, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:35, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:35, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2018 02:35, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2018 15:30, sampling point TF101 | Combined Uranium 4006 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2021 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2018 15:45, sampling point TF102 | Combined Uranium 4006 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2021 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Apr 23, 2018 02:25, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2017 – Dec 31, 2019 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Apr 23, 2018 01:55, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2017 – Dec 31, 2019 |
-
- Collected
- Jun 15, 2019 04:48
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 190628-042PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.3572 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jun 4, 2019 03:58
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- 190605-004HA
- Laboratory
- MSDH Lab
-
Monochloroacetic Acid 2450 EPA method 552.2
- Result
- Not detected below 0.002 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Dichloroacetic Acid 2451 EPA method 552.2
- Result
- 0.002 mg/l
- Monitoring period
- Not recorded
-
Trichloroacetic Acid 2452 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Monobromoacetic Acid 2453 EPA method 552.2
- Result
- 0.012 mg/l
- Monitoring period
- Not recorded
-
Dibromoacetic Acid 2454 EPA method 552.2
- Result
- 0.005 mg/l
- Monitoring period
- Not recorded
-
Total Haloacetic Acids (Haa5) 2456
- Result
- 0.019 mg/l
- Monitoring period
- Jan 1, 2019 – Dec 31, 2019
-
- Collected
- Jan 29, 2019 15:09
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 190130-049NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2019 – Dec 31, 2019
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jan 29, 2019 14:48
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 190130-005NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2019 – Dec 31, 2019
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Sep 17, 2018 02:11
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 180918-028IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0047 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Barium 1010 EPA method 200.8
- Result
- 0.1112 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Chromium 1020 EPA method 200.8
- Result
- 0.0035 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Fluoride 1025 EPA method 300.0
- Result
- 0.443 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.0026 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
- Collected
- Sep 17, 2018 02:35
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 180918-027IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0106 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Barium 1010 EPA method 200.8
- Result
- 0.1463 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Chromium 1020 EPA method 200.8
- Result
- 0.0042 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Fluoride 1025 EPA method 300.0
- Result
- 0.434 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Nickel 1036 EPA method 200.8
- Result
- 0.0006 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.0041 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
- Collected
- Jul 9, 2018 15:30
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 180710-040RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2013 – Dec 31, 2021
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jul 9, 2018 15:45
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 180710-031RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2013 – Dec 31, 2021
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Apr 23, 2018 02:25
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 180424-033CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Apr 23, 2018 01:55
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 180424-006CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
Routine (10).