Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Chemical and radiological sample results

MS0250105 , Hinds Co Detention Center-Gallatin St

4 of the 31 analytes this system has been tested for have been detected at least once, across 2 samples on record.

The other 27 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 2 samples on record, detections range from June 23, 2026 to July 23, 2026. These figures cover the whole record; the list of samples further down is narrowed.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for Hinds Co Detention Center-Gallatin St, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Combined Radium (-226 & -228) 4010 Radionuclide 1 of 1 result Jul 23, 2026 Jul 23, 2026
Radium-226 4020 Radionuclide 1 of 1 result Jul 23, 2026 Jul 23, 2026
Nitrate-Nitrite 1038 Inorganic Chemical 1 of 1 result Jun 23, 2026 Jun 23, 2026
Nitrate 1040 Inorganic Chemical 1 of 1 result Jun 23, 2026 Jun 23, 2026

Showing samples collected between September 25, 2024 and September 25, 2026. That is this page’s default, not a limit on what the agency records.

Show every sample on record

Choose a date range

The most recent samples, result by result

The 2 samples collected between September 25, 2024 and September 25, 2026 are listed below, newest first.

31 results from the 2 samples listed here: 4 detected, 27 not detected. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for Hinds Co Detention Center-Gallatin St, every result from the 2 samples on record, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Jul 23, 2026 10:00
Sampling point
TF101 Treatment Plant TF101
Sample type
Routine
Lab sample
810-201579-1
Laboratory
Eurofins Eaton Analytical South Bend in
Not detected below 3 pci/l Minimum Reporting Level , sample collected Jul 23, 2026 10:00, sampling point TF101 Gross Alpha, Excl. Radon & U 4000 Not recorded
Not detected below 3 pci/l Minimum Reporting Level , sample collected Jul 23, 2026 10:00, sampling point TF101 Gross Alpha, Incl. Radon & U 4002 EPA method 7110B Not recorded
Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 23, 2026 10:00, sampling point TF101 Combined Uranium 4006 EPA method 200.8 Jul 1, 2026 – Sep 30, 2026
0.49 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Jul 23, 2026 10:00, sampling point TF101 Combined Radium (-226 & -228) 4010 Jul 1, 2026 – Sep 30, 2026
0.49 pci/l , sample collected Jul 23, 2026 10:00, sampling point TF101 Radium-226 4020 EPA method 7500-RAB Not recorded
Not detected below 1 pci/l Minimum Reporting Level , sample collected Jul 23, 2026 10:00, sampling point TF101 Radium-228 4030 EPA method 7500-RAD Not recorded
Collected
Jun 23, 2026
Sampling point
TF101 Treatment Plant TF101
Sample type
Routine
Lab sample
35046063001
Laboratory
Pace Analytical Services, LLC
Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Cyanide 1024 EPA method 335.4 Jan 1, 2026 – Dec 31, 2031
0.09 mg/l , sample collected Jun 23, 2026, sampling point TF101 Nitrate-Nitrite 1038 Apr 1, 2026 – Jun 30, 2026
0.09 mg/l , sample collected Jun 23, 2026, sampling point TF101 Nitrate 1040 EPA method 353.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.05 mg/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Nitrite 1041 EPA method 353.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 1,2,4-Trichlorobenzene 2378 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Cis-1,2-Dichloroethylene 2380 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 1 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Xylenes, Total 2955 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 1 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Dichloromethane 2964 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 O-Dichlorobenzene 2968 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 P-Dichlorobenzene 2969 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Vinyl Chloride 2976 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 1,1-Dichloroethylene 2977 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Trans-1,2-Dichloroethylene 2979 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 1,2-Dichloroethane 2980 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 1,1,1-Trichloroethane 2981 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Carbon Tetrachloride 2982 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 1,2-Dichloropropane 2983 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Trichloroethylene 2984 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 1,1,2-Trichloroethane 2985 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Tetrachloroethylene 2987 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Chlorobenzene 2989 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Benzene 2990 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Toluene 2991 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Ethylbenzene 2992 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 23, 2026, sampling point TF101 Styrene 2996 EPA method 524.2 Apr 1, 2026 – Jun 30, 2026

Routine (2).